Cat.6 STP is mainly used for connections in building horizon-tal cables, EDA, HDA and other areas of the data center.
• Cat.6 STP features high-quality electrical and mechanical performance that exceeds the requirements of ISO/IEC11801 and ANSI/TIA-568.2-D standards.
• Compact cable design.
• Data twisted pairs are suitable for structured cabling, and can be used to transmit digital signals or analog voice, video and data signals.
• Applicable to the Power over Ethernet.
Technical specifications:
| Content | Technical Index |
|---|---|
| Maximum resistance imbalance | 2% |
| Insulation resistance | >5000MΩ·km |
| Characteristic impedance | 4-250MHz 100±15Ω |
| Delay skew | ≤45ns/100m |
| Operation Temperature |
Installation Temperature: -20°C to +60°C Operation Temperature: -40°C to +70°C Cold bending: -20°C×4h no crack |
| Permissible bending radius during installation | Not less than 8 times the outer diameter of the twisted pair. |
| Bending radius | Static for 10 times the cable diameter, dynamic for 20 times the cable diameter. |
| Maximum tension | 400N |
| Maximum conductor resistance | 85Ω/km (23AWG) |
| Insulating material | HDPE |
| Minimum insulation resistance Dielectric strength |
100MΩ/km 500Vac/1min |
| Package | 305m/box |